Sinumerik Alarm 27241 PROFIsafe: DP M version different, NCK: %1, PLC: %2


Sinumerik Alarm 27241 PROFIsafe: DP M version different, NCK: %1, PLC: %2

Parameters:
%1 = DP interface version of the NCK %2 = DP interface version of the PLC

Definitions:
The NCK and PLC components have different implementations of the DP interface. The F communication cannot be initialized.

Reactions:
– Mode group not ready.
– Channel not ready.
– NC Start disable in this channel.
– NC Stop on alarm.
– Alarm display.
– Interface signals are set.

Remedy:
Check the PLC operating system and NCK software versions. Upgrade the PLC operating system. Delete the NCK F parameterization.

Program Continuation:
Switch control OFF – ON.