Sinumerik Alarm 27095 %1 SPL protection not activated
Parameters:
%1 = Name of the component on which the protection is not activated (NCK or PLC)
Definitions:
The protection features are not activated for the SPL. The startup phase of the SPL is not yet complete. No stop reaction (Stop D) was initiated on an error in data cross-comparison between NCK and PLC.
Reactions:
– Alarm display.
Remedy:
• Remedy for NCK: Activate the protection features with MD $MN_PREVENT_SYNACT_LOCK[0,1]. The number range of the synchronized action IDs used in the SPL must be entered in this MD.
• Remedy for PLC: Activate the protection features by setting the appropriate data bit in DB18.
Program Continuation:
Clear alarm with the RESET key. Restart part program
References
- Siemens Diagnostics Guide by Siemens