Sinumerik Alarm 380060 Profibus-DP: alarm %1 on logical address %2 from unassigned station
Parameters:
%1 = Alarm class
%2 = Logical address
Definitions:
SDB1000 contains a slave which is not assigned in the NC via the MD parameters (see the help for alarm 380 050/51). The slave is also connected to the PROFIBUS DP. An alarm has been triggered by a slave of this type. Alarm class:
• 01 = Station return (or arrival)
• 02 = Station failure Operation with the NC is not possible.
Reactions:
– Alarm display.
Remedy:
• Enter machine data or
• Modify SDB1000 or
• Disconnect the slave from PROFIBUS DP or
• Acknowledge the alarm.
Program Continuation:
Clear alarm with the Delete key or NC START.