Sinumerik Alarm 12160 Channel %1 block %2 range of values exceeded


Sinumerik Alarm 12160 Channel %1 block %2 range of values exceeded

Parameters:
%1 = Channel number
%2 = Block number, label

Definitions:
The programmed constant or the variable exceeds the value range that has previously been established by the definition of data type.

Reactions:
– Alarm display.
– Interface signals are set.
– Correction block

Remedy:
Press the NC Stop key and select the function “Correction block” with the soft key PROGRAM CORRECT. The correction pointer positions on the incorrect block. Correct value of the constant or adapt data type. If the value for an integer constant is too great, it can be specified as real constant by adding a decimal point.
Example:
R1 = 9 876 543 210 Correct: R1 = 9 876 543 210.
Value range INTEGER: Value range REAL: 2-1022 to 2+1023

Program Continuation:
Clear alarm with NC START or RESET key and continue the program.