Sinumerik Alarms
Siemens Sinumerik Alarms Errors SINUMERIK 840D/840Di/810D
Sinumerik Alarm 100302 No data available – or no access authorization
Sinumerik Alarm 100302 No data available – or no access authorization Definitions: The list image can not be generated, as this data is currently not available. Example: Local user data…
Sinumerik Alarm 100301 The table cannot be completely generated
Sinumerik Alarm 100301 The table cannot be completely generated Definitions: The list image could not be generated due to insufficient memory. Reactions: – – Remedy: System error, a rebooting may…
Sinumerik Alarm 100300 xxx not found
Sinumerik Alarm 100300 xxx not found Definitions: The search term entered in a list image (e.g. general machine data) was not found. Reactions: – – Remedy: – Program Continuation: Internal
Sinumerik Alarm 26012 Axis %1 QEC: feed forward control not active
Sinumerik Alarm 26012 Axis %1 QEC: feed forward control not active Parameters: %1 = Axis name, spindle number Definitions: The error criterion for determining the quadrant error necessitates a correctly…
Sinumerik Alarm 75607 Channel %1 resynchronisation not possible
Sinumerik Alarm 75607 Channel %1 resynchronisation not possible Parameters: %1 = Channel number Definitions: The block search triggered by the compile cycle has been terminated with an error. It can…
Sinumerik Alarm 75606 Channel %1 retraceable contour was shortened
Sinumerik Alarm 75606 Channel %1 retraceable contour was shortened Parameters: %1 = Channel number Definitions: The block search buffer is full. Therefore the retraceable contour had to be shortened. Reactions:…
Sinumerik Alarm 75605 Channel %1 retrace support: internal error, error code %2
Sinumerik Alarm 75605 Channel %1 retrace support: internal error, error code %2 Parameters: %1 = Channel number %2 = Error code Definitions: With this alarm, RESU-internal error states are displayed…
Sinumerik Alarm 75601 Channel %1 block %2 invalid parameter in CC_PREPRE()
Sinumerik Alarm 75601 Channel %1 block %2 invalid parameter in CC_PREPRE() Parameters: %1 = Channel number %2 = Block number, label Definitions: Only the values –1, 0, 1 are valid…
Sinumerik Alarm 75600 Channel %1 retrace support: wrong MD configuration. Error code %2
Sinumerik Alarm 75600 Channel %1 retrace support: wrong MD configuration. Error code %2 Parameters: %1 = Channel number %2 = Error code Definitions: The following errors were detected in the…
Sinumerik Alarm 75500 Channel %1 wrong configuration
Sinumerik Alarm 75500 Channel %1 wrong configuration Parameters: %1 = Channel number Definitions: There are two causes of this alarm: – No geometry axis has been defined – The option…
Sinumerik Alarm 75452 Axis %1 setpoint switchover not possible in the current state
Sinumerik Alarm 75452 Axis %1 setpoint switchover not possible in the current state Parameters: %1 = Axis name Definitions: The axes included in the setpoint exchange group are not all…
Sinumerik Alarm 75451 Error with definition of setpoint switchover
Sinumerik Alarm 75451 Error with definition of setpoint switchover Definitions: Exchange axis number and machine axis number are identical, gaps have been defined, or the machine axis number is the…
Sinumerik Alarm 75275 Channel %1 block %2 working area error
Sinumerik Alarm 75275 Channel %1 block %2 working area error Parameters: %1 = Channel number %2 = Block number, label Definitions: The programmed point is not within the working range…
Sinumerik Alarm 75270 Channel %1 tool parameters incorrect
Sinumerik Alarm 75270 Channel %1 tool parameters incorrect Parameters: %1 = Channel number Definitions: The tool parameters are not the same as the settings for the handling transformation package (checked…
Sinumerik Alarm 75265 Channel %1 block %2 working area error
Sinumerik Alarm 75265 Channel %1 block %2 working area error Parameters: %1 = Channel number %2 = Block number, label Definitions: The programmed point is not within the working range…
Sinumerik Alarm 75260 Channel %1 block %2 tool parameters incorrect
Sinumerik Alarm 75260 Channel %1 block %2 tool parameters incorrect Parameters: %1 = Channel number %2 = Block number, label Definitions: The tool parameters are not the same as the…
Sinumerik Alarm 75255 Channel %1 working area error
Sinumerik Alarm 75255 Channel %1 working area error Parameters: %1 = Channel number Definitions: The programmed point is not within the working range of the kinematic (checked in interpreter). Reactions:…
Sinumerik Alarm 75250 Channel %1 tool parameters incorrect
Sinumerik Alarm 75250 Channel %1 tool parameters incorrect Parameters: %1 = Channel number Definitions: The tool parameters are not the same as the settings for the handling transformation package (checked…
Sinumerik Alarm 75210 Channel %1 number of axes/axis assignment inconsistent
Sinumerik Alarm 75210 Channel %1 number of axes/axis assignment inconsistent Parameters: %1 = Channel number Definitions: The number of axes specified in MD TRAFO 6_NUM_AXES and the number of axes…
Sinumerik Alarm 75200 Channel %1 wrong MD configuration, %2 incorrect
Sinumerik Alarm 75200 Channel %1 wrong MD configuration, %2 incorrect Parameters: %1 = Channel number %2 = Machine data Definitions: A window in machine data %2 has been detected during…
Sinumerik Alarm 75110 Axis %1 reached drift limit
Sinumerik Alarm 75110 Axis %1 reached drift limit Parameters: %1 = Axis name Definitions: The automatic drift compensation has reached the value set in MD 36710 $MA_DRIFT_VALUE. Reactions: – Alarm…
Sinumerik Alarm 75100 Too many analog axes configured
Sinumerik Alarm 75100 Too many analog axes configured Definitions: More than 3 NC axes are configured as analog axes in machine data 63530 $MA_ANALOG_AXIS. Reactions: – Alarm display. Remedy: Reduce…
Sinumerik Alarm 75071 Channel %1 collision monitoring axis %2
Sinumerik Alarm 75071 Channel %1 collision monitoring axis %2 Parameters: %1 = Channel number %2 = Axis name Definitions: Collision monitor has responded. Reactions: – Alarm display. Remedy: Traverse the…
Sinumerik Alarm 75070 Channel %1 wrong machine data for collision protection %2
Sinumerik Alarm 75070 Channel %1 wrong machine data for collision protection %2 Parameters: %1 = Channel number %2 = Axis name Definitions: Incorrect machine data for collision protection. Reactions: –…
Sinumerik Alarm 75062 Channel %1 axes not in standstill axis %2
Sinumerik Alarm 75062 Channel %1 axes not in standstill axis %2 Parameters: %1 = Channel number %2 = Axis name Definitions: The CC_Master and/or CC_Slave axes were not at standstill…
Sinumerik Alarm 75061 Channel %1 coupling active axis %2
Sinumerik Alarm 75061 Channel %1 coupling active axis %2 Parameters: %1 = Channel number %2 = Axis name Definitions: Machine data MD 63000: CC_MASTER_AXIS has been changed when the coupling…
Sinumerik Alarm 75060 Channel %1 tolerance window exceeded axis %2
Sinumerik Alarm 75060 Channel %1 tolerance window exceeded axis %2 Parameters: %1 = Channel number %2 = Axis name Definitions: The actual value difference between the CC_Slave axis %2 and…
Sinumerik Alarm 75051 Channel %1 CC_COPON CC_COPOFF error code %2
Sinumerik Alarm 75051 Channel %1 CC_COPON CC_COPOFF error code %2 Parameters: %1 = Channel number %2 = Error code Definitions: %2 = 1 Wrong argument programmed %2 = 10 An…
Sinumerik Alarm 75050 Channel %1 wrong MD configuration, error code %2
Sinumerik Alarm 75050 Channel %1 wrong MD configuration, error code %2 Parameters: %1 = Channel number %2 = Error code Definitions: Incorrect configuration in MD $MA_CC_MASTER_AXIS %2 = 2 This…
Sinumerik Alarm 75025 Channel %1 CLC stopped because sensor head has been touched
Sinumerik Alarm 75025 Channel %1 CLC stopped because sensor head has been touched Parameters: %1 = Channel number Definitions: The collision monitor of the sensor tip has signaled “Sensor touched”….
Sinumerik Alarm 75021 Channel %1 CLC position offset at upper limit %2
Sinumerik Alarm 75021 Channel %1 CLC position offset at upper limit %2 Parameters: %1 = Channel number %2 = Limit value Definitions: The position offset generated by the overlaid motion…
Sinumerik Alarm 75020 Channel %1 CLC position offset at lower limit %2
Sinumerik Alarm 75020 Channel %1 CLC position offset at lower limit %2 Parameters: %1 = Channel number %2 = Limit value Definitions: The position offset generated by the overlaid motion…
Sinumerik Alarm 75016 Channel %1 block %2 CLC: orientation changed for TRAFOOF
Sinumerik Alarm 75016 Channel %1 block %2 CLC: orientation changed for TRAFOOF Parameters: %1 = Channel number %2 = Block number Definitions: 1. The 2D/3D clearance control has been switched…
Sinumerik Alarm 75015 Channel %1 block %2 CLC(0) with active TOC
Sinumerik Alarm 75015 Channel %1 block %2 CLC(0) with active TOC Parameters: %1 = Channel number %2 = Block number Definitions: The 3D clearance control has been switched off with…
Sinumerik Alarm 75010 Channel %1 block %2 CLC_LIM value exceeds MD limit
Sinumerik Alarm 75010 Channel %1 block %2 CLC_LIM value exceeds MD limit Parameters: %1 = Channel number %2 = Block number Definitions: One of the limits for the position offset…