Sinumerik Alarm 300003 Axis %1 drive %2 wrong module type %3


Sinumerik Alarm 300003 Axis %1 drive %2 wrong module type %3

Parameters:
%1 = NC axis number
%2 = Drive number
%3 = Incorrect module type

Definitions:
The hardware configuration of the drive components established at the time of bus initialization does not correspond to the information in machine data 13030 DRIVE_MODULE_TYPE[p]=… (p … rack location index).

Reactions:
– NC not ready.
– Channel not ready.
– NC Stop on alarm.
– NC Start disable in this channel.
– The NC switches to follow-up mode.
– Alarm display.
– Interface signals are set.

Remedy:
Please inform the authorized personnel/service department. Enter MD 13030 DRIVE_MODULE_TYPE to match the drive modules that are plugged in. Select MD 13010 DRIVE_LOGIC_NR and search for the drive logic number that is indicated in the alarm text. The location index number + 1 results in the associated rack location number. The VDD module belonging to this location is determined by the configuration in MD 13030 DRIVE_MODULE_TYPE for the same location index. Input value 1: 1-axis module, input value 2: 2-axis module.

Program Continuation:
Switch control OFF – ON.