Sinumerik Alarm 300004 Axis %1 drive %2 wrong drive type %3 (FDD/MSD)


Sinumerik Alarm 300004 Axis %1 drive %2 wrong drive type %3 (FDD/MSD)

Parameters:
%1 = NC axis number
%2 = Drive number
%3 = Drive type code

Definitions:
A feed module is inserted in the rack location determined by the drive logic number, but in the corresponding NCK-specific MD 13040 DRIVE_TYPE, a main spindle is defined (or vice versa).

Reactions:
– NC not ready.
– Channel not ready.
– NC Stop on alarm.
– NC Start disable in this channel.
– The NC switches to follow-up mode.
– Alarm display.
– Interface signals are set.

Remedy:
Please inform the authorized personnel/service department. Select MD 13010 DRIVE_LOGIC_NR and search for the drive logic number that is indicated in the alarm text. The location index number + 1 results in the associated rack location number. The FDD/MSD module belonging to this location is determined by the configuration in MD 13040 DRIVE_TYPE for the same location index. FDD: identifier 1, MSD: identifier 2.

Program Continuation:
Switch control OFF – ON.