Sinumerik Alarm 300005 At least one module found on drive bus that has not been configured
Definitions:
At bus initialization at least one module was detected which did not have a drive number, which amounts to one too many. Since all (!) modules on the drive bus must be correctly initialized, all modules therefore also have to be accordingly specified in the machine data.
Reactions:
– NC not ready.
– Channel not ready.
– NC Stop on alarm.
– NC Start disable in this channel.
– The NC switches to follow-up mode.
– Alarm display.
– Interface signals are set.
Remedy:
Please inform the authorized personnel/service department. Check machine data; with the NCK MD 13000 DRIVE_IS_ACTIVE a drive that is not yet in use but exists on the bus can be declared as inactive. Inactive drives do not need installation and start-up or drive data.
Program Continuation:
Switch control OFF – ON.