Sinumerik Alarm 300778 Axis %1 drive %2 generator mode: converter frequency rotor position identification


Sinumerik Alarm 300778 Axis %1 drive %2 generator mode: converter frequency rotor position identification

Parameters:
%1 = NC axis number
%2 = Drive number

Definitions:
When selecting the rotor position identification (MD1011 bit 12 or bit 13) only converter frequencies (MD1100) of 4 kHz/8 kHz are permissible.
• Modify MD 1011: $MD_ACTUAL_VALUE_CONFIG (actual value sensing configuration IM)
• Modify MD 1100: $MD_PWM_FREQUENZY (pulse width modulation frequency) The alarm can be reprogrammed in the MD ALARM_REACTION_CHAN_NOREADY (channel not ready).

Reactions:
– NC not ready.
– Channel not ready.
– Channel not ready.
– NC Stop on alarm.
– NC Start disable in this channel.
– The NC switches to follow-up mode.
– Alarm display.
– Interface signals are set.

Remedy:
Please inform the authorized personnel/service department. Change the converter frequency (MD 1100) or deselect rotor position identification (MD1011 bit 12 or bit 13).
• Modify MD 1011: $MD_ACTUAL_VALUE_CONFIG (actual value sensing configuration IM)
• Modify MD 1100: $MD_PWM_FREQUENZY (pulse width modulation frequency)

Program Continuation:
Clear alarm with the RESET key in all channels. Restart part program.