Sinumerik Alarm 300861 Axis %1 drive %2 generator mode: minimum axis speed > max. motor speed
Parameters:
%1 = NC axis number
%2 = Drive number
Definitions:
The value in MD1635: $MD_GEN_AXIS_MIN_SPEED $MD_GEN_AXIS_MIN_SPEED (minimum generator axis speed) is greater than the value in MD1146: $MD_MOTOR_MAX_ALLOWED_SPEED (maximum motor speed).
Reactions:
– Alarm display.
– Interface signals are set.
Remedy:
Please inform the authorized personnel/service department.
• Modify MD 1635: $MD_GEN_AXIS_MIN_SPEED generator axis) or
• Modify MD 1146: $MD_MOTOR_MAX_ALLOWED_SPEED (maximum motor speed).
Program Continuation:
Alarm display showing cause of alarm disappears. No further operator action